Holman et al v. W-Industries of Louisiana, LLC
Filing
162
MEMORANDUM RULING re 118 MOTION for Summary Judgment filed by U P Systems Inc. Signed by Judge Robert G James on 1/22/15. (crt,Crawford, A)
UNITED STATES DISTRICT COURT
WESTERN DISTRICT OF LOUISIANA
MONROE DIVISION
DENNIS E. HOLMAN AND
YOLANDA HOLMAN
CIVIL ACTION 11-1864
VERSUS
JUDGE ROBERT G. JAMES
W-INDUSTRIES OF LOUISIANA, LLC,
MAG. JUDGE KAREN L. HAYES
ET AL.
RULING
Pending before the Court is a Motion for Summary Judgment [Doc. No. 118] filed by
Defendant UP Systems, Inc., and its Custom Power Division (“UP Systems”). Plaintiffs Dennis and
Yolanda Holman (“the Holmans”) have filed an opposition memorandum [Doc. No. 124], and UP
Systems has filed a reply memorandum [Doc. No. 130].
For the following reasons, the Motion for Summary Judgment is GRANTED.
I.
FACTS AND PROCEDURAL HISTORY
UP Systems is a manufacturer of uninterrupted power equipment that is routinely used in
offshore applications. Essentially, the equipment is a series of rechargeable batteries.
Plaintiff Dennis Holman (“Holman”) worked as a production operator for Greystar
Corporation (“Greystar”) aboard the ATP Titan, a complex structure serving as both a drilling
platform and production facility in the Telemark Field in the Gulf of Mexico. The Holmans brought
this personal injury lawsuit after Holman slipped and fell while working on the ATP Titan.
In October of 2007, UP Systems manufactured nineteen pieces of equipment, including
twelve battery chargers, which were intended to provide an uninterrupted power supply to the ATP
Titan. The equipment was installed by other contractors and/or shipyard personnel and incorporated
into the ATP Titan’s electrical system.1
The ATP Titan’s Process Control System (“PCS”) monitored and controlled processes on
the platform when in normal operating ranges. The Process Safety System (“PSS”), also known as
the Emergency Safety System, took over in emergency situations when the processes were operating
outside normal ranges. The PSS monitored and controlled UP Systems’ equipment, which provided
backup battery power. In turn, the PSS was controlled by the Programmable Logic Control (“PLC”),
which is the “brain for the platform.” [Doc. No. 118, Exh. A, Deposition of Cody Dupre (“Dupre
Depo.”), p. 85]. All automated devices on the platform were ultimately controlled by the PLC.
Problems with UP Systems’ equipment, including the 12208/4502B battery charger2 at issue
in this litigation, would manifest through the ATP Titan’s common alarm system and display a fault
via several screens located in the control room manned by Greystar.
Shortly before Holman’s slip and fall, at Greystar’s direction, W-Industries installed a shunt
trip on the 12208 battery charger. Before installation of the shunt trip, if the voltage or current
dropped below a set value on the battery charger’s low voltage relay, an alarm would be triggered,
but the battery charger would continue to operate. The shunt trip is a “circuit breaker that, in
addition to tripping on overloads, can be tripped electronically; [sic] for example, at a designated low
voltage.” [Doc. No. 118, p. 3, n. 6]. After installation of the shunt trip, if the voltage dipped below
1
According to UP Systems, its equipment was installed incorrectly in a horizontal
position. [Doc. No. 118, Deposition of Richard Reed (“Reed Depo.”), Exh. B, p. 59].
2
The battery charger has been identified by both numbers, but, for ease of reference, the
Court will hereafter refer only to the 12208 identification number. See [Doc. No. 130, Exh. F,
Depo. of Richard Reed, p. 58, lines 1-3 (Q: . . “And I think we’ve established that 12208 is
4502B; is that right?” A: “Correct, uh-huh.”).
2
the set value, an alarm would still be triggered, but the breaker would also trip, causing the battery
charger to stop operating.
The battery chargers operated on a 24-volt system. When UP Systems manufactured the
equipment, the low voltage relay factory setting should have been 21 volts, and the factory relay
setting should not have been changed after installation. In order to change the setting, someone
would have to use a small screwdriver to turn the relay from one setting to another. However,
according to Greystar’s lead instruments and electrical (“I & T”) technician, Cody Dupre (“Dupre”),
over time, vibrations on the platform can also “walk” the setting either higher or lower. [Doc. No.
118, Exh. A, Dupre Depo., p. 66].3
While W-Industries was installing the shunt trips, UP Systems’ technician, Richard Reed
(“Reed”), came to the ATP Titan to service the equipment. He was on the platform to address a
number of issues with the equipment, including problems with battery chargers 12207 and 12208
which had previously caused the system to go on battery power on or about October 24, 2010. [Doc.
No. 130, Exh. F, Reed Depo., pp. 84-85]. This incident had prompted an email from Jason Martinez
(“Martinez”) of W-Industries to Patrick Thomas (“Thomas”) of UP Systems, but the email was not
shown to Reed, and the October 24 incident was not the only reason Reed was on the ATP Titan.
According to Reed, the UP Systems equipment was “quite a nasty mess” because it had been
improperly installed horizontally. [Doc. No. 130, Exh. F., Reed Depo., p. 58]. In addition to working
3
Dupre explained that the “setting is controlled by a little pot that you turn with a real
small screwdriver . . . to determine the twenty-three (23) or twenty-one (21) or whatever you
want it at. Vibration over time can walk that little pot, okay? So in the past I’ve seen where
shunt trips tripped accidentally, you know, because it’s vibrated itself to a lower setpoint or a
higher setpoint . . . .” [Doc. No. 118, Exh. A, Dupre Depo., p. 66].
3
with W-Industries on installation of the shunt trips, Reed addressed problems with several battery
chargers and problems in the hull.
As part of his work, Reed did troubleshoot the October 24th incident when the system went
on battery power, but found no problems with the hardware or bad fuses. [Doc. No. 130, Exh. F.,
Reed Depo., p. 89]. On October 30, 2010, Reed also performed work on the 12208 battery charger
to ensure that the link between the W-Industries shunt trip and the battery charger would not cause
false alarms, but would indicate actual problems with the system.4 Reed has “no recollection of
having to make or check any adjustments” to the low voltage setting on the 12208 battery charger
relay. [Doc. No. 118, Exh. B, Reed Depo., p. 92].5 Reed did not perform any further work on the
12208 battery charger after October 30th, and Reed’s records showed that he had not made
adjustments to the relay for this battery charger during other trips to the ATP Titan. Id.; see also id.
at Exh. D.
After completing work on the 12208 battery charger, Reed remained on the ATP Titan,
performing other work on UP Systems’ equipment. Reed finished his work and left the ATP Titan
on the afternoon of November 3, 2010.
4
Reed characterizes his work as advisory because the W-Industries technicians were
performing the actual installation. [Doc. No. 130, Exh. F., Reed Depo, p. 89].
5
Q:
“And would it be your testimony that there would be no reason, the work that you
would have been doing during November–October, November, for you to make
any adjustments to the relay in connection with the installation of the shunt trips
or any of the other work you were doing at the time?”
A:
“I have no recollection of having to make or check any adjustments.”
[Doc. No. 130, Exh. F., Reed Depo., p. 92].
4
In the late afternoon or early evening of November 3, 2010, the current dipped below 23
volts, an alarm sounded, the Greystar control room was notified of a problem, and the shunt trip
caused the circuit breaker to trip battery charger 12208. However, Dupre had told Greystar personnel
to ignore the alarms generated by the battery chargers because of the ongoing work on the battery
chargers. The Greystar control room employees ignored the alarms, which continued over the next
five and one-half hours, and consequently the battery for the PSS circuit was drained. The ATP
Titan’s PLC then allegedly interpreted the drained battery as a “worst case scenario,” such as an
explosion or fire, causing the Emergency Shut Down and Deluge System (“ESDDS”) to activate.
On the date of the incident, Holman was in the galley eating cereal. He heard a loud “boom”
and felt the platform sway. [Doc. No. 120, Exhibit A, Holman Depo., pp. 89-90].6 Shortly thereafter,
at approximately 10:30 p.m., the emergency shut-in alarm sounded, and the lights went out.
There were allegedly reports of a gas release from the process area. In response, Holman’s
supervisor, Deral Cox (“Cox”), sent him below the platform to “kill the electrical pump” and stop
any release. Id.
Because the water deluge system had begun to operate, spraying the platform with tens of
thousands of gallons of water in order to suppress a potential fire, the piping and deck were wet and
slippery. Hydrocarbons on the stairs also made them slippery. As Holman ascended a stairwell, his
grip slipped, and he stumbled backwards, falling down the stairs and injuring his back.
6
It was later determined that a crane operator employed by Nabors Drilling USA, LP
(“Nabors”) had caused the sound when he allowed a grocery box to hit the handrail near the
living quarters. However, in the Ruling [Doc. No. 142] on Nabors’ Motion for Summary
Judgment, the Court found insufficient evidence to raise a genuine issue of material fact for trial
that the impact of the grocery box caused the ensuing emergency activation. Thus, the Court
granted Nabors’ Motion for Summary Judgment and dismissed all claims against this defendant.
[Doc. No. 143].
5
After the accident, Holman returned to the control room. By that time, the lights were back
on, and the emergency generator was operating. Holman was off the remainder of his shift and was
taken to shore by helicopter the next day. He did not return to work.
Dupre investigated the emergency activation incident (not Holman’s slip and fall) and found
that the low voltage relay for battery charger 12208 had been set at 23 volts.7 In his opinion, the
incorrect setting is what caused the ensuing events. Because Reed had recently worked on the 12208
battery charger, as well as other UP Systems’ equipment, Dupre assumed and stated in his report that
Reed had changed the setting. However, neither Dupre nor anyone else saw Reed set the low voltage
relay at 23 volts. During his deposition, Dupre also admitted that he did not want the stunt trips
installed because he had previous experience with vibrations on a platform causing the relay setting
to “walk” up or down.
After the November 3, 2010 incident, Dupre contacted UP Systems and was given permission
and instructions on how to re-set the system to 21 volts.
The shunt trips were removed
approximately one week later. There were no further incidents after Dupre re-set the low voltage
relay.8 If the low voltage relay had been set at 21 volts, the loss of power would likely never have
occurred.9
On October 21, 2011, the Holmans brought suit against W-Industries of Louisiana, LLC (“WIndustries”), asserting claims under the Outer Continental Shelf Lands Act (“OCSLA”). The
7
UP Systems raises an issue as to whether Dupre used the proper method to determine the
setting, but, for purposes of summary judgment, the Court assumes that Dupre was correct, and
the low voltage relay was set at 23 volts.
8
Although these facts may constitute subsequent remedial measures, the Court includes
them solely to provide a complete history of the events.
9
[Doc. No. 124, Exh. 24, Reed Depo., p. 103; Exh. 39, Dupre Depo., p. 106].
6
Holmans originally alleged that W-Industries, which performed repair and maintenance services on
the ATP Titan, was liable because its technicians negligently set the low voltage “trip level” for the
ESDDS at 23 volts, which ultimately caused the scenario resulting in Holman’s incident. Mrs.
Holman also asserted a loss of consortium claim under Louisiana law.
On June 1, 2012, with leave of Court, the Holmans amended their Complaint. [Doc. No. 13].
As it was unclear whether the ATP Titan might be considered a vessel, rather than a platform, the
Holmans amended to assert a maritime claim. The Holmans also added Emerson Network Power,
Liebert Services, Inc. (“Emerson”), alleging that an Emerson employee was responsible for the 23volt setting.
On August 10, 2012, W-Industries filed a cross-claim against Emerson and a third party
demand against ATP Oil & Gas Corporation (“ATP”), Greystar, Mustang Engineering, L.P.
(“Mustang”), Bluewater Industries, Inc. (“Bluewater”), and Nabors Drilling USA, LP (“Nabors”).
[Doc. No. 23]. W-Industries later amended its cross-claim and third party demand to add MMR
Group, Inc. (“MMR”) as another third party defendant. [Doc. No. 26].
On October 1, 2012, ATP filed a suggestion of bankruptcy, resulting in a stay of proceedings
against it. [Doc. Nos. 31 & 32].
On February 12, 2013, the Holmans filed a Second Supplemental and Amending Complaint,
adding claims against UP Systems. The Holmans alleged that “an employee of Custom Power, a
division of UP Systems . . . , was responsible for mistakenly setting the emergency shutdown
mechanisms at a level at variance with the plans and specifications for such system, and further that
such action caused the shutdown system to mistakenly activate, causing an emergency evacuation
to initiate on the ATP Titan on the night of November 3, 2010, resulting in [Holman’s] injury. [Doc.
7
No. 57, ¶ I]. The Holmans contend that UP Systems is “responsible for the negligent acts of its
employee . . . either solely, or along with the other Defendants.” Id. The Holmans then explained
that they had mistakenly named Emerson and moved to dismiss their claims against that defendant.
Id. at ¶ II.
On April 2, 2013, Mustang Engineering asserted a cross-claim against UP Systems [Doc. No.
68], and UP Systems asserted a cross claim against ATP, Bluewater, Greystar, Mustang, Nabors, and
W-Industries. [Doc. No. 69].
On April 8, 2013, the Court granted UP Systems’ motion to dismiss its cross-claim against
ATP. [Doc. No. 72].
On August 13, 2013, the Court granted a motion for stay filed by Greystar, staying the case
until the issuance of a decision by the United States Court of Appeals for the Fifth Circuit in the case
of Warrior Energy Services, Corp. v. ATP Titan M/V, Case No. 13-30587. [Doc. No. 89].
On August 19, 2013, the Court granted the Motion for Summary Judgment filed by MMR
and dismissed all claims against it. [Doc. No. 91].
On January 30, 2014, the Court lifted its stay and granted the Motion for Summary Judgment
filed by Greystar. [Doc. No. 96]. Relying on the Fifth Circuit’s final binding opinion in Warrior
Energy that the ATP Titan is a non-vessel, the Court found that Greystar is immune from tort
liability in this case. Thus, the Court dismissed all claims against Greystar.
On March 20, 2014, the Court granted W-Industries’ voluntary motion to dismiss its claims
against Bluewater, Nabors, and Mustang without prejudice. [Doc. No. 99].
On June 23, 2014, the Holmans filed a Third Supplemental and Amended Complaint adding
Nabors as a Defendant. [Doc. No. 104].
8
On October 10, 2014, UP Systems filed the instant Motion for Summary Judgment [Doc. No.
118]. On the same day, Nabors filed a Rule 12(c) Motion for Judgment on the Pleadings [Doc. No.
119] and a Motion for Summary Judgment [Doc. No. 120].
On October 30, 2014, the Holmans filed a Memorandum in Opposition to UP Systems’
Motion for Summary Judgment. [Doc. No. 127].
On December 15, 2014, the Court granted the Motion for Summary Judgment filed by
Nabors and dismissed all claims against it. Nabors’ Motion for Judgment on the Pleadings and a
pending motion in limine were denied as moot. [Doc. No. 144].
On December 30, 2014, the Court granted W-Industries’ voluntary motion to dismiss claims
against ATP without prejudice. [Doc. No. 149].
On January 2, 2015, the Court was notified that the Holmans and W-Industries had amicably
resolved their claims.
The Court is now prepared to rule on UP Systems’ Motion for Summary Judgment.
II.
LAW AND ANALYSIS
A.
Standard of Review
Summary judgment “should be rendered if the pleadings, the discovery and disclosure
materials on file, and any affidavits show that there is no genuine issue as to any material fact and
that the movant is entitled to judgment as a matter of law.” FED . R. CIV . P. 56(c)(2). The moving
party bears the initial burden of informing the court of the basis for its motion by identifying portions
of the record which highlight the absence of genuine issues of material fact. Topalian v. Ehrmann,
954 F.2d 1125, 1132 (5th Cir. 1992). A fact is “material” if proof of its existence or nonexistence
would affect the outcome of the lawsuit under applicable law in the case. Anderson v. Liberty
9
Lobby, Inc., 477 U.S. 242, 248 (1986). A dispute about a material fact is “genuine” if the evidence
is such that a reasonable fact finder could render a verdict for the nonmoving party. Id.
If the moving party can meet the initial burden, the burden then shifts to the nonmoving party
to establish the existence of a genuine issue of material fact for trial. Norman v. Apache Corp., 19
F.3d 1017, 1023 (5th Cir. 1994). The nonmoving party must show more than “some metaphysical
doubt as to the material facts.” Matsushita Elec. Indus. Co., Ltd. v. Zenith Radio Corp., 475 U.S.
574, 586 (1986). In evaluating the evidence tendered by the parties, the Court must accept the
evidence of the nonmovant as credible and draw all justifiable inferences in its favor. Anderson, 477
U.S. at 255.
B.
Negligence
The Holmans’ claims against UP Systems are governed by the OCSLA, which applies
Louisiana’s negligence law.10 To determine whether a plaintiff should recover on a negligence
claim, Louisiana courts employ a duty-risk analysis. Long v. State ex rel. Dept. of Transp. and Dev.,
04-0486 (La. 6/29/05); 916 So.2d 87, 101. Under the duty-risk analysis, a plaintiff must demonstrate
that (1) the defendant had a duty to conform to a specific standard of care (duty); (2) the defendant
failed to conform its conduct to that standard (breach); (3) the defendant’s substandard conduct was
a cause-in-fact of the plaintiff’s injuries (cause-in-fact); (4) the defendant’s substandard conduct was
a legal cause of the plaintiff’s injuries (legal causation or scope of liability); and (5) that the plaintiff
10
As UP Systems correctly notes, if the Holmans claimed that the UP Systems’ equipment
was defective in any way, their recovery would be limited by the Louisiana Products Liability
Act (“LPLA”). However, despite multiple amendments to their Complaint, the Holmans have
not alleged design or manufacturing defect in the battery charger 12208, only negligence. The
Holmans state in their opposition to the pending motion that “in all likelihood this problem had
“existed from the time of its initial manufacturer and testing by [UP Systems’] Custom Power
[Power Division] at its Houston facility,” but still do not assert a products liability claim. [Doc.
No. 124, p. 7].
10
suffered actual damages (damages). See Mathieu v. Imperial Toy Corp., 94-C-0952, p. 5 (La.
11/30/94); 646 So.2d 318, 322 (citations omitted); Long, 916 So.2d at 101 (citations omitted). A
plaintiff’s failure to prove any of the elements of the duty-risk analysis results in a determination of
no liability. Lemann v. Essen Lane Daiquiris, Inc., 05–1095 (La. 3/10/06); 923 So.2d 627.
UP Systems raises five arguments to support its Motion for Summary Judgment: (1) res ipsa
loquitor does not apply, (2) UP Systems had no legal duty to protect Holman from his slip and fall,
(3) UP Systems’ alleged negligence was not a legal cause of Holman’s accident, (4) UP Systems’
alleged negligence was not a cause-in-fact of Holman’s accident, and, (5) even if UP Systems’
alleged negligence was a cause-in-fact of Holman’s accident, the intervening and superseding
negligence of Greystar relieves UP Systems of liability. For the following reasons, the Court finds
that UP Systems is entitled to summary judgment because UP Systems breached no duty to the
Holmans, res ipsa loquitor is inapplicable, and, in the alternative, even if UP Systems breached a
duty, its breach was not a legal cause of Holman’s accident. Given these conclusions, the Court
resolves the case without reaching the remainder of UP Systems’ arguments.
1.
Duty, Breach of Duty, and Res Ipsa Loquitor
“The threshold issue in any negligence action is whether the defendant owed the plaintiff a
duty, and whether a duty is owed is a question of law.” Hanks v. Entergy Corp., 2006–477, p. 21
(La. 12/18/06); 944 So.2d 564, 579. “The inquiry is whether the plaintiff has any law—statutory,
jurisprudential, or arising from general principles of fault—to support his claim.” Hardy v. Bowie,
99–2821 (La. 9/8/99), 744 So.2d 606, 614. Assuming that such a duty is established, the plaintiff
in a negligence action must also show that the defendant failed to conform its conduct to the
applicable standard, i.e., that it breached a duty owed to the plaintiff. Mathieu, 646 So.2d at 322.
11
A plaintiff may meet its evidentiary burden by providing direct or circumstantial evidence, or, if
applicable, by relying on the doctrine of res ipsa loquitor.
In its Motion for Summary Judgment, UP Systems argues that there is no direct evidence that
Reed changed the low voltage relay setting, as the Holmans asserted in their Second Supplemental
and Amending Complaint, and the doctrine of res ipsa loquitor cannot provide a presumption of
liability. UP Systems argues further that it had no legal duty through Reed “to confirm that the
settings on [Greystar’s] equipment remained unchanged from their original factory settings, much
less to protect against slip and fall injuries.” [Doc. No. 118, p. 21]. Ultimately, UP Systems contends
that it had no duty to guarantee the platform’s overall safety and no duty to ensure that Greystar
employees, including Holman, “safely respond to emergency procedures.” [Doc. No. 118, pp. 2122].
In opposition, the Holmans argue that Reed either negligently set the low voltage relay at 23
volts, or he breached his duty to detect and correct the low voltage relay setting that “[i]n all
likelihood existed from the time of [battery charger 12208’s] initial manufacture and testing by [UP
Systems] . . . at its Houston facility.” [Doc. No. 124, p. 7]. In support of their argument that Reed
should have detected the improper low voltage relay setting, the Holmans point to an October 24,
2010 incident where the platform lost 24-volt power from the charger. This specific incident
prompted a request from W-Industries’ technician, Martinez, to Thomas of UP Systems to send out
Reed. Given Reed’s knowledge that a low voltage incident occurred, the Holmans contend that he
(and, through him, UP Systems), had a duty to check and correct the low voltage relay setting. He
allegedly breached that duty and set in motion the chain of events resulting in Holman’s slip and fall
12
accident. The Holmans admit that the doctrine of res ipsa loquitor is inapplicable, but contend that
they have presented sufficient other evidence of UP Systems’ duty and breach.
In its reply memorandum, UP Systems points out that the Holmans’ original theory that
Reed changed the setting to 23 volts has been “debunked,” and they can no longer rely on this
alleged duty. UP Systems then argues that the Holmans cannot establish negligence based on their
new theories because they cannot prove that the low voltage relay setting was improperly set at 23
volts at the time of manufacture, and Reed “had no contractual duty to re-set the allegedly improperly
set low voltage relay.” [Doc. No. 130, pp. 4-5].
Assuming that UP Systems had a duty to initially set the low voltage relay at 21 volts and/or
to leave that setting at 21 volts, the Court finds insufficient evidence to raise a genuine issue of
material fact for trial whether those duties were breached. As UP Systems argues and as the
Holmans admit, this is not a case where the doctrine of res ipsa loquitor applies and would permit
an inference of negligence as to either of these two theories.11 There is no direct evidence to support
the Holmans’ theory that the incorrect low voltage relay setting existed from the time of UP Systems’
manufacture of the equipment in 2007. If Reed or someone else did not change the setting in the
ensuing three years, there is only speculation that the improper setting had existed since the time of
manufacture. Speculation, of course, is not competent summary judgment evidence.
11
The doctrine of res ipsa loquitur, which means “the thing speaks for itself,” permits an
inference of negligence when a plaintiff establishes three criteria: that the injury is one which
ordinarily does not occur in the absence of negligence, the evidence must sufficiently eliminate
other more probable causes of the injury, and that the negligence of the defendant falls within the
scope of his duty to plaintiff. Linnear v. Centerpoint Energy Entex/Reliant Energy, 2006–3030
(La.9/5/07), 966 So.2d 36, 41 (quoting Linnear v. CenterPoint Energy Entex/Reliant Energy,
06-41171 (La. App. 2 Cir. 8/4/06), 945 So.2d 1, 8).
13
There is also no direct evidence that Reed adjusted the setting on the 12208 battery charger
low voltage relay to 23 volts. Reed denies changing the setting. Although Dupre, Greystar’s lead
I & E technician, initially stated in his report that Reed adjusted the setting, when deposed, he
admitted that he had no personal knowledge that Reed did so. Further, though Dupre claimed that
only UP Systems’ employees worked on its battery chargers,12 W-Industries employee, Martinez,
testified that Greystar and W-Industries employees also worked on the system (although Martinez
also denied changing the setting). Finally, Dupre admitted that, in his experience, vibrations on the
platform can sometimes “walk” the low voltage relay setting up or down over time.
Having found that UP Systems could not have breached any duty owed based on these
arguments, the Court must consider the Holmans’ new argument--that the low voltage issue on
October 24, 2010, imposed on Reed a duty to check the low voltage relay setting. If he had done so,
the Holmans argue that he would have changed that setting to 21 volts, and none of the events of
November 3, 2010, would have occurred.
There is no specific statutory or jurisprudential authority which creates the duty argued by
the Holmans. Instead, the Court must consider the general principles of fault. Certainly, Reed had
a duty, like any other technician, to exercise the appropriate care in performance of his repair and
troubleshooting tasks. Reed came to the ATP Titan to perform a number of tasks, including issues
with several battery chargers, problems with the hull, checking the problem with loss of power that
occurred on October 24, 2010, and working with W-Industries on the installation of shunt trips for
12
Dupre explained that only UP Systems technicians were supposed to work on its
equipment because of the warranty. However, the warranty on the equipment had expired in late
2009, approximately one year before the November 3, 2010 incident. It is undisputed that after
the November 3, 2010 incident, Dupre contacted UP Systems, obtained permission and
instructions on changing the low voltage relay setting to 21 volts, and, apparently, changed the
setting.
14
battery chargers. Yet, after carefully reviewing the record, the Court finds insufficient evidence,
based on the facts and circumstances of this case, that Reed had a duty to specifically check the low
voltage relay setting on battery charger 12208 and change it to 21 volts.
The Court has considered the testimony of Martinez, Dupre, and Reed. In an email to UP
Systems supervisor, Thomas, after the October 24, 2010 incident, Martinez explained:
On 10/24/10 the chargers tripped the output breakers on a low DC voltage alarm
but did not send the “common trouble” alarm to the control room. The control
system ran on batteries for an unknown amount of time until it shut down. We had
no way of charging the batteries to bring them up past the shutdown point. . . .
[Doc. No. 124, Exh. 14, Deposition of Patrick Thomas (emphasis added)]. In his deposition,
Martinez testified that, as a result of the October 24, 2010 incident:
[the] platform lost 24-volt from one of these chargers. That’s when we started
looking into what happened. And, apparently, one of those low voltage relays tripped
before performing the function it needed to. Probably on a low, low voltage[,] and
it shut off. So, that’s the gist of what–why I sent this here.
[Doc. No. 124, Exh. 12, Deposition of Jason Martinez, p. 12 (emphasis added)].
Although he did not personally review Martinez’s email, Reed was aware of the October 24,
2010 incident. He testified that he did check the low voltage problem, but found “no hardware
failure” and no “bad fuses” that would have caused the problem. [Doc. No. 130, Exh. F, Reed
Depo., p. 89]. Reed was questioned in his deposition if he should have checked the low voltage relay
setting, but responded that he had “no recollection of having to make or check any adjustments”
to the low voltage setting on the 12208 battery charger relay. [Doc. No. 118, Exh. B, Reed Depo.,
p. 92 (emphasis added)]. Thus, the evidence before the Court shows that there was some type of low
voltage problem, that the assigned UP Systems’ technician checked that problem, and that, based on
his expertise, he found no need to check the low voltage relay setting.
15
Finally, the Court reviewed the testimony of Greystar’s Dupre. He testified that, while Reed
was on the ATP Titan, they tested “undervoltage/overvoltage and the ground fault.” [Doc. No. 118,
Exh. A, Dupre Depo., p. 73]. He explained further:
Q:
What do the unvervoltage/overvoltage tests consist of?
A:
To go ahead and create an overvoltage alarm, make the relay pick up, watch
it trip the breaker to make sure everything was wired right. And then create
an undervoltage scenario and do the same thing, and then create a ground
fault scenario and make sure it showed up at the control room at the charger
itself and activated the shunt trip, the breaker.
Id. Although someone, not just Reed, could have read the meter, no one knew at what voltage the
tests were performed. Id. at p. 74.
After considering all this testimony, the Court cannot find, as a matter of law, that UP
Systems owed a duty to Greystar and its employees, including Holman, to check and detect the low
voltage relay setting on battery charger 12208. The Court is aware that Reed’s testimony serves the
interests of his employer, but his testimony stands unrebutted that he performed all tasks he was
assigned on the ATP Titan, including a check of the equipment based on the October 24, 2010
incident. Based on his skills and experience, Reed did not believe he needed to check the low
voltage relay on battery charger 12208. Dupre’s testimony confirms that undervoltage/overvoltage
tests were conducted, but does not create an issue of fact whether Reed saw, should have seen, or
needed to see the voltage setting to perform the tests.13 Nor have the Holmans produced any other
evidence that rebuts Reed’s testimony and creates the legal duty they assert.
13
Dupre is not a disinterested witness either, but the Court finds no issues of credibility
for the jury to resolve. The Court has credited the testimony of both these witnesses. Even so,
there is insufficient evidence that Reed had a duty as a matter of law to check the low voltage
relay setting.
16
The Holmans have not produced competent summary judgment evidence that Reed, and
hence UP Systems, failed to conform his conduct to the applicable standard of care. Without this
evidence and because the Holmans admittedly do not and cannot rely on res ipsa loquitor, the
Holmans cannot establish negligence. Therefore, UP Systems’ Motion for Summary Judgment
should be granted on this basis alone.
2.
Legal Cause
The Court is aware, however, of the ambiguity in case law on how broadly or narrowly to
construe the duty element. Indeed, it has been observed that “the duty element in the five-part
formulation of the negligence-law cause of action has been called an ‘unnecessary fifth wheel on the
coach, incapable of sound analysis and possibly productive of injustice.’” DAVID W. ROBERTSON ,
Allocating Authority Among Institutional Decision Makers in Louisiana State-Court Negligence and
Strict Liability Cases, 57 La. L. Rev. 1079, 1092 (1997). Nevertheless, even assuming arguendo that
the Holmans could establish the duty and breach of duty elements, the Court finds, in the alternative,
that they have failed to establish that such breach was the legal or proximate cause of Holman’s
injuries.
Legal cause is known as the scope of liability or scope of protection element. The Louisiana
Supreme Court has found that there is no “‘rule’” for determining the scope of duty. Roberts v.
Benoit, 605 So.2d 1032, 1044 (La. 1991). “Regardless if stated in terms of proximate cause, legal
cause, or duty, the scope of the duty inquiry is ultimately a question of policy as to whether the
particular risk falls within the scope of the duty.” Id. (citing Edwards v. State, 556 So.2d 644,
648–49 (La. App. 2d Cir. 1990)). “[D]etermination of legal cause involves a purely legal question,”
but “this legal determination depends on factual determinations of foreseeability and ease of
17
association.” Rando v. Anco Insulations Inc., 08–1163 (La.5/22/09), 16 So.3d 1065, 1088 (citing
Todd v. State, Dep’t. of Social Servs., 96-3090 (La. 9/9/97), 699 So.2d 35, 39). A risk may not be
found within the scope of the duty where the circumstances of that injury to the plaintiff could not
reasonably be foreseen or anticipated because there was no ease of association between the risk of
that injury and the legal duty. See Weaver v. Valley Elec. Membership Corp., 615 So.2d 1375, 1383
(La. App. 2 Cir., 1993). “The ease of association of the injury with the rule of conduct that is urged,
however, is the proper inquiry.” Id. (citing W. PROSSER, Law of Torts (3d Ed.1964) at 282 ff;
DAVID ROBERTSON , Reason Versus Rule In Louisiana Tort Law: Dialogues On Hill v. Lundin &
Associates, Inc., 34 La .L. Rev. 1 (1973)). “The extent of protection owed a particular plaintiff is
determined on a case-to-case basis to avoid making a defendant an ‘insurer’ of all persons against
all harms. Id. (citations omitted).
For the Holmans to establish legal cause, they would have to show that Holman’s slip and
fall on the stairs was within the scope of Reed’s alleged duty to check the low voltage relay setting.
The Court finds no ease of association between the alleged duty and Holman’s injuries. As UP
Systems points out, its equipment functioned as it should. On November 3, 2010, when the current
dipped below 23 volts, the alarm sounded, and the Greystar control room was notified that there was
a problem. Additionally, the shunt trip, which had been installed by W-Industries for Greystar, also
worked correctly, causing the 12208 battery charger to “trip” and stop functioning.14
In order for the Holmans to establish legal causation, it must have been reasonably
foreseeable to UP Systems that Reed’s failure to check the low voltage relay setting would result in
14
Even though W-Industries was primarily responsible for installing the shunt trips, Reed
coordinated with W-Industries and would have been aware that, if the current dipped below the
low voltage relay setting, the 12208 battery charger would trip. Thus, there would be an ease of
association with an injury caused by the tripping of the battery charger.
18
Holman’s injury from a slip and fall on wet and oily stairs when (1) Dupre failed to tell Greystar
control room employees that battery charger 12208 was now functional, and any alarms should be
checked; (2) Greystar control room employees ignored the alarm sounded by the UP Systems’
equipment for five and one-half hours, draining the batteries; (3) the PLC, or the “brain” for the
platform, would interpret the drained batteries as a worst case scenario; and (4) Greystar would send
Holman to check on a pump below the platform, even though the stairs were wet and oily and even
though they had not yet determined the cause of the emergency (or even if there was an emergency).
While the low voltage relay setting may have initiated the chain of events, the Court finds that UP
Systems could not have reasonably anticipated Holman’s accident and injury. Accordingly, UP
Systems is entitled to summary judgment on this alternative basis.
III.
CONCLUSION
For the foregoing reasons, UP Systems’ Motion for Summary Judgment [Doc. No. 118] is
GRANTED, and all claims against UP Systems are DISMISSED WITH PREJUDICE.
MONROE, LOUISIANA, this 22nd day of January, 2015.
19
Disclaimer: Justia Dockets & Filings provides public litigation records from the federal appellate and district courts. These filings and docket sheets should not be considered findings of fact or liability, nor do they necessarily reflect the view of Justia.
Why Is My Information Online?