Tex Pat, LLC v. United Technologies Corporation et al

Filing 1

COMPLAINT against Detector Electronics Corporation, UTC Fire & Security Corporation, United Technologies Corporation ( Filing fee $ 350 receipt number 0540-2739937.), filed by Tex Pat, LLC. (Attachments: # 1 Exhibit A, # 2 Exhibit B, # 3 Exhibit C, # 4 Exhibit D, # 5 Exhibit E, # 6 Exhibit F, # 7 Civil Cover Sheet)(Ni, Hao)

Download PDF
Tex Pat, LLC v. United Technologies Corporation et al Doc. 1 Att. 5 EXHIBIT E Dockets.Justia.com SPECIFICATION DATA UVIR Flame Detector X5200 DESCRIPTION F E AT u R E S The evolution continues with the new X5200 UVIR Flame Detector. The X5200 combines the technologies used in the X2200 and X9800 to provide unparalleled detection capabilities and immunity to extraneous sources, combined with a superior mechanical design. The mounting Wa r r a n t Y arrangement allows the UV and IR sensors to monitor the same hazardous location with a 90 degree cone of vision. When both sensors simultaneously detect the presence of a flame, an alarm signal is generated. The detector has Division and Zone explosion-proof ratings and is suitable for use in indoor and outdoor applications. Y 3 e a r The standard output configuration includes fire, fault and auxiliary relays. An optional 4 to 20 mA output can be provided in addition to the three relays. A model with pulse output is available for easy retrofitting into existing Det-Tronics controller based systems. Auxiliary relay and 4 to 20 mA output are not available with the pulse model. A tricolor LED on the detector faceplate indicates detector status condition. The X5200 housing is available in aluminum or stainless steel, with NEMA 4X and IP66 rating. Typical applications include: -- Munitions -- Petrochemical applications -- Turbines. * oi is Detector Electronics' Trademark for its patented Optical Integrity Systems, U.S. Patent 3,952,196, United Kingdom Patent 1,534,969, Canada Patent 1,059,598. · FM 3260 (2000). · EN 54-10 Certified (VdS). · ATEX Directive compliant. · EQP models available. · New patented signal processing, TDSA, Arc. · A new level of false alarm rejection. · Responds to a fire in the presence of modulated blackbody radiation (i.e. heaters, ovens, turbines) without false alarm. · High speed capability. · Microprocessor controlled heated optics for increased resistance to moisture and ice. · Automatic, manual or magnetic optical integrity (oi) testing -- no external test lamp required. · Easily replaceable oi plate. · Fire, fault and auxiliary relays standard. · MODBUS RS-485 communication. · 4 to 20 mA isolated output (optional). · Pulse output for compatibility with controller based systems (optional). · Tricolor LED indicates normal operation, fire and fault conditions. · Mounting swivel allows easy sighting. · Integral wiring compartment for ease of installation. · Class A wiring per NFPA-72. · Meets NFPA-33 response requirement for under 0.5 second (available when model selected). · RFI and EMC Directive compliant. · Built-in data logging / event monitoring. 4/07 90-1156 2.2 © Detector Electronics Corporation 2007 S P E C I F I C AT I O N S Operating Voltage Power Consumption 24 vdc. Operating range is 18 to 30 vdc. 2.8 watts @ 24 vdc minimum. 17.5 watts @ 30 vdc with EOL resistor installed and heater on maximum. Contacts rated 5 amperes at 30 vdc. Fire Alarm: Certification ® FM ® FM Class I, Div. 1, Groups B, C & D; Class II, Div. 1, Groups E, F, & G; Class I, Div. 2, Groups A, B, C & D (T3); Class II, Div. 2, Groups F & G (T3); Class III. NEMA/Type 4X. APPROVED APPROVED Relays FM APPROVED Fault: -- Form C (NO and NC contacts) -- normally de-energized -- latching/non-latching. -- Form A (NO contacts) -- normally energized -- latching/non-latching. -- Form C (NO and NC contacts) -- normally energized -- latching/non-latching. Increased Safety Model 0539 II 2 GD EEx de IIC T5­T6 T86°C DEMKO 02 ATEX 132195 T6 (Tamb = ­55°C to +60°C). T5 (Tamb = ­55°C to +75°C). IP66. ® Auxiliary*: Current Output* (Optional) Temperature Range 4­20 mA, with a maximum loop resistance of 500 ohms from 18­19.9 vdc, 600 ohms from 20­30 vdc. Operating: Storage: ­40°F to +167°F (­40°C to +75°C). ­67°F to +185°F (­55°C to +85°C). IECEx Certificate of Conformity IECEx ULD 06.0018X Ex d IIC T5-T6 or Ex de IIC T5-T6 T6 (Tamb = ­55°C to +60°C). T5 (Tamb = ­55°C to +75°C). FM APPROVED Flameproof Model 0539 II 2 GD EEx d IIC T5­T6 T86°C DEMKO 02 ATEX 132195 T6 (Tamb = ­55°C to +60°C). T5 (Tamb = ­55°C to +75°C). IP66. ® Dimensions Dimensions shown in inches (centimeters). Humidity Range 0 to 95% relative humidity, can withstand 100% condensing humidity for short periods of time. The X5200 has a 90 degree cone of vision with the highest sensitivity lying along its central axis. 3 years. Copper-free aluminum or 316 stainless steel. 3/4 inch NPT or 25 mm. Aluminum: Stainless Steel: 6 pounds (2.7 kg). 10 pounds (4.5 kg). 4.7 (11.9) Field of View Warranty Enclosure Material Conduit Entry Size Shipping Weight (Approximate) Response Characteristics A2142 9.7 (24.6) 4.8 (12.2) Wiring 14 AWG (2.08 mm2) or 16 AWG (1.31 mm2) shielded cable is recommended. 9 8 7 6 5 4 3 2 1 4-20 mA + 4-20 mA + REF COM FIRE N.O. FIRE N.C. FIRE COM FAULT N.O. FAULT 24 VDC + 24 VDC ­ 19 18 17 16 15 14 13 12 11 4-20 mA ­ 4-20 mA ­ REF SPARE SPARE COM AUX N.O. AUX N.C. AUX RS-485 A RS-485 B MAN Oi 29 28 27 26 25 24 23 22 21 A2061 Very High Sensitivity UV & IR, Low Arc, TDSA On, Quick Fire On Fuel n-Heptane Methane NOTE: Size 1 x 1 foot 32 inch plume Distance Feet (M) 85 (25.9) 65 (19.8) Typical Response Time (Seconds) 14 5 24 VDC ­ Refer to the X5200 instruction manual (form number 95-8546) for details regarding detector response. Wiring Terminal Identification for Standard X5200 *Auxiliary relay and 4 to 20 mA output are not available on pulse output model. G T IS ED ER BY UL AN D BS Detector Electronics Corporation 6901 West 110th Street · Minneapolis, Minnesota 55438 USA Operator: (952) 941-5665 or (800) 765-FIRE Customer Service: (952) 946-6491 · Fax (952) 829-8750 http://www.det-tronics.com · E-mail: detronics@detronics.com I RE ISO 9001 REGIS NO . S REGI TER ED FIR TE RED FI RM M A 23 8 05 · NO. 25 26 Specifications subject to change without notice.

Disclaimer: Justia Dockets & Filings provides public litigation records from the federal appellate and district courts. These filings and docket sheets should not be considered findings of fact or liability, nor do they necessarily reflect the view of Justia.


Why Is My Information Online?